BLOCK DIAGRAM — ONLINE VIBRATION MONITORING (Online CMS) × INOVA360 SUPERVISION Tongon Gold Mine (Barrick) — Côte d'Ivoire · functional architecture, single-line · Revision F INOVATEC Level 3 — Technical room Level 2 — OT network Level 1 — Acquisition Level 0 — Field Technical room · standalone system, independent from SCADA CMS server Dedicated 2U server or virtual machine — IT/OT decision Redundant power supplies · site NTP time-stamping RAID 1 · mirrored volume SKF @ptitude Observer + Microsoft SQL Server Machine models · SKF bearing geometry database Fault frequencies BPFO · BPFI · BSF · FTF Time-stamped history — indicators, spectra, waveforms D1 D2 Simultaneous write read-only Control workstation Supervision · expert analysis · maintenance management INOVA360 — operational supervision Dashboard, prioritised alarms, trends, reports · web and mobile SKF @ptitude Observer — analysis client (2 licences) Spectra, envelope, waterfalls, waveforms · phase on the pumps CMMS — notifications and work orders Interfacing to be defined with Tongon — outside budget baseline OT core switch Dedicated CMS VLAN · SNMP managed OM3 fibre converters OM3 multimode fibre-optic backbone — dedicated VLAN ARM-01 · Grinding 1 3 × SKF Multilog IMx-8 20 AI channels · 4 spare No tachometer input 230 VAC → 24 VDC redundant Store & forward (edge, 4 GB) ARM-02 · Grinding 2 3 × SKF Multilog IMx-8 20 AI channels · 4 spare No tachometer input 230 VAC → 24 VDC redundant Store & forward (edge, 4 GB) ARM-03 · Pumping 4 × SKF Multilog IMx-8 32 voies AI · 0 spare — extension = +1 module 4 speed inputs (D1) — pump tachometers 230 VAC → 24 VDC redundant Store & forward (edge, 4 GB) ARM-04 · Crushing — OPTION 2 EXTENSION — 3 × SKF Multilog IMx-8 20 AI channels · 4 spare 230 VAC → 24 VDC redundant Store & forward (edge, 4 GB) BALL MILL 01 31-MILL-01 8 MW · 995 rpm · non-VSD 16 vib. channels + 4 temp. IEPE 100 mV/g · PT100 cl. A Trunnions: 500 mV/g, out of scope Trunnions: rolling or plain bearings — to confirm BALL MILL 02 32-MILL-01 8 MW · 995 rpm · non-VSD 16 vib. channels + 4 temp. IEPE 100 mV/g · PT100 cl. A Trunnions: 500 mV/g, out of scope Trunnions: rolling or plain bearings — to confirm CYCLONE PUMP 31-PUMP-01 600 kW · VSD 1490 rpm 6 vib + 2 temp + 1 tachometer IEPE 100 mV/g NU 328-C3 / 6322-C3 CYCLONE PUMP 31-PUMP-02 600 kW · VSD 1490 rpm 6 vib + 2 temp + 1 tachometer IEPE 100 mV/g NU 328-C3 / 6322-C3 CYCLONE PUMP 32-PUMP-01 600 kW · VSD 1490 rpm 6 vib + 2 temp + 1 tachometer IEPE 100 mV/g NU 328-C3 / 6322-C3 CYCLONE PUMP 32-PUMP-02 600 kW · VSD 1490 rpm 6 vib + 2 temp + 1 tachometer IEPE 100 mV/g NU 328-C3 / 6322-C3 JAW CRUSHER 21-CRUS-01 200 kW · 990 rpm 8 vib. + 2 temp. IEPE 100 mV/g NU 322-C3 / 6319-C3 Eccentric shaft: speed to be measured Option 2 extension JAW CRUSHER 22-CRUS-01 200 kW · 990 rpm 8 vib. + 2 temp. IEPE 100 mV/g NU 322-C3 / 6319-C3 Eccentric shaft: speed to be measured Option 2 extension OT network — OM3 multimode fibre optic, dedicated VLAN Measurement cable — shielded multicore + low-noise coaxial IP66 field junction box Liaison logicielle interne — read-only Option 1 — mills + pumps · 72 AI channels + 4 tacho · 10 modules Option 2 extension — concasseurs · parc complet 92 voies AI · 13 modules INOVA360 and CMMS interfacing are outside the budget baseline and priced separately. Installation independent from SCADA — no OPC UA gateway to the process. INOVA360 is fed read-only from Observer and never writes to the CMS. Sensors specified by interface (IEPE, 4–20 mA); commercial references in the BOM. 500 mV/g accelerometers and ATEX equipment out of scope. Provisional layouts pending the site survey and the SKF review. Issuer INOVATEC — Smart Infrastructure, Abidjan Project / Client Online CMS — Tongon Gold Mine (Barrick), Côte d'Ivoire Title Block diagram — functional architecture × INOVA360 Reference INOV-TGM-CMS-SYN-001 Revision F Date August 2026 Stage / Format Proposal — A3 landscape